Certification Record |
|
| CUSTOMER |
CLASS |
FILE |
|
| Marathon Special Products Corp. |
6228-01 |
019766_0_000 |
| 13300 Van Camp Rd, PO Box 468 |
WIRE CONNECTING DEVICES-Terminal Assemblies |
|
| Bowling Green |
| OH |
| 43402 |
|
|
| USA |
Refer to Class Description for program details |
TO THE REQUIREMENTS OF CSA STD. C22.2 NO 158-1987 (REAFFIRMED 1991):
- Terminal blocks, for solid and stranded copper wire, with max ratings of Series/Cat Nos
as follows:
Series 200, 200H: For line and load terminals:
Wire Binding Screws: Wire sizes range Nos 12-20 AWG solid, Nos 12-22 AWG stranded,
rated 20A max, 300V, torque 9 lb in.
Captive pressure wire clamp screws: Wire size range Nos 12-22 AWG stranded only,
rated 20A max, 300V, torque 12 lb in.
Quick connect terminals: For wire size range Nos 10-16 AWG, 30A max.
|
Termination
and Wire Range |
Termination
and Wire Range |
Rating
Amp (Max), Volts |
| Series/Cat No |
Line (AWG) |
Load (AWG) |
150V 300V 600V |
| 100 |
(1)SCR, QC, |
(1)SCR, QC, SOL, |
10 |
| 300 |
(1)SCR, QC, |
(1)SCR, QC, SOL, |
20A, 600V |
| 400 |
(1)SCR, QC, |
(1)SCR, QC, SOL, |
40A, 600V |
| 140x303 |
(1)P 350MCM-6 |
(1)P 350MCM-6 |
310A Cu, 600V |
| x401 |
(1)P 2/0-14 |
(6)P 4-14 |
175A, 600V |
| 402 |
(1)P 2/0-14 |
(4)P 4-14 |
175A, 600V |
| x404 |
(1)P 350MCM-6 |
(6)P 4-14 Cu |
310A Cu, 600V |
|
|
(6)P 4-12 Al |
250A Al, 600V |
| 411 |
(1)P 3/0-14 |
(4)P 4-14 |
200A, 600V |
| 801 |
(1)P 250MCM-6 |
(1)P 250MCM-6 |
255A, 600V |
| 901 |
(1)P 2/0-14 |
(6)P 4-14 |
175A, 600V |
| 902 |
(1)P 2/0-14 |
(4)P 4-14 |
175A, 600V |
| 141x100 |
(1)SCR 10-16 |
(1)SCR 10-16 |
40A, 600V |
| 200 |
(1)P 2-14 |
(1)SCR 10-16 |
115A, 600V |
| 201 |
(1)P 2-14 |
(1)T 10-18 |
115A, 600V |
| 202 |
(1)P 2-14 |
(4)QC 10-18 |
115A, 600V |
| 203 |
(1)P 2-14 |
(1)S |
115A, 600V |
| 204 |
(1)P 2-14 |
(1)SCR 12-22 |
20A, 600V |
| 205 |
(1)P 2-14 |
(1)T and |
115A, 600V |
| 300 |
(1)P 2-14 |
(1)P 2-14 |
115A, 600V |
| 301 |
(1)P 2-14 |
(1)P 2-14 and |
115A, 300V |
| 400 |
(1)P 2-14 |
(4)P 10-18 |
115A, 600V |
| 401 |
(1)P 2-14 |
(3)P 10-18 |
90A, 600V |
| 141x402 |
(1)P 2-14 |
(3)P 10-18 and |
115A, 600V |
| 403 |
(1)P 2-14 |
(2)P 10-18 and |
60A, 600V |
| 142x120 |
(1)P 2/0-14 |
(1)P 2/0-14 |
175A, 600V |
| 121-CU |
(1)P 1/0-6 |
(1)P 1/0-6 |
150A, 600V |
| 122-CU |
(1)S |
(1)S |
200A, 600V |
| 123-CU |
(1)SCR |
(1)SCR |
200A, 600V |
| 133x126 |
(1)P 350kcmil-6 |
(1)P 350kcmil-6 |
310A, 600V |
| 270 |
(1)S M10 |
(4)P 2/0-14 |
510A, 600V |
| 271 |
(1)S 3/8-16 |
(4)P 2/0-14 |
510A, 600V |
| 272 |
(1)S 3/8-16 |
(12)P 4-14 |
510A, 600V |
| 273 |
(1)S M10 |
(12)P 4-14 |
510A, 600V |
| 280 |
(1)S M10 |
(8)P 2-14 |
510A, 600V |
| 281 |
(1)S 3/8-16 |
(8)P 2-14 |
510A, 600V |
| 305 |
(2)P 2/0-14 |
(2)P 2/0-14 |
350A, 600V |
| 320 |
(2)P 250kcmil-6 |
(2)P 250kcmil-6 |
510A, 600V |
| 360 |
(1)P 600kcmil-2 |
(1)P 600kcmil-2 |
420A, 600V |
| 552 |
(1)P 400kcmil-4 |
(4)P 2-14 |
335A, 600V |
| 555 |
(2)P 2/0-14 |
(6)P 4-14 |
350A, 600V |
| 558 |
(1)P 350kcmil-6 |
(1)S M10 |
310A, 600V |
| 559 |
(1)P 350kcmil-6 |
(1)S 3/8-16 |
310A, 600V |
| 563 |
(1)S 3/8-16 |
(1)S 3/8-16 |
310A, 600V |
| 564 |
(1)S M10 |
(1)S M10 |
310A, 600V |
| 565 |
(1)P 600kcmil-2 |
(2)P 250kcmil-6 |
420A, 600V |
| 575 |
(1)P 600kcmil-2 |
(4)P 2/0-14 |
420A, 600V |
| 585 |
(1)P 600kcmil-2 |
(8)P 2-14 |
420A, 600V |
| 587 |
1(P) 500kcmil-4 |
(1)P 350kcmil-6 (3)P
2-14 |
380A, 600V |
| 588 |
(1)P 600kcmil-2 |
(3)P 1/0-14 (6)P
2-14 |
420A, 600V |
| 595 |
(1)P 600kcmil-2 |
(12)P 4-14 |
420A, 600V |
| 596 |
(2)P 250kcmil-6 |
(12)P 4-14 |
510A, 600V |
| 597 |
(2)P250kcmil-6 |
(8)P 2-14 |
510A, 600V |
| 598 |
(2)P 250kcmil-6 |
(4)P 2/0-14 |
510A, 600V |
| 953 |
(1)P 500kcmil-4 |
(6)P 2-14 |
380V, 600V |
| 955 |
(2)P 2/0-14 |
(6)P 4-14 |
350V, 600V |
| 301 |
(1)P 2/0-14 |
(1)P 2/0-14 and |
175A, 600V |
| 406 |
(1)P 3/0-14 |
(4)P 4-14 |
200A, 600V |
| 411 |
(1)P 2/0-14 |
(1)T |
175A, 600V |
| 551 |
(1)P 2/0-14 |
(1)P 2/0-14 |
175A, 600V |
| 552 |
(1)P 2-14 |
(1)P 2-14 |
115A, 600V |
| 553 |
(1)P 2/0-14 |
(1)T |
175A, 600V |
| 570 |
(1)P 2/0-14 |
(4)P 4-14 |
175A, 600V |
| 572 |
(1)P 2/0-14 |
(1)P 2/0-14 |
175A, 600V |
| 574 |
(1)P 2/0-14 |
(1)S |
175A, 600V |
| 575 |
(1)P 1/0-6 |
(1)P 1/0-6 |
150A, 600V |
| 579 |
(1)P 2/0-14 |
(1)P 2/0-14 |
175A, 600V |
| 970-CU |
(1)P 2/0-14 |
(4)P 4-14 |
175A, 600V |
| 143x123 |
(1)P 250MCM-6 |
(1)P 250MCM-6 |
255A, 600V |
| 124-CU |
(1)P 250MCM-6 |
(1)P 250MCM-6 |
255A, 600V |
| 126 |
(1) 350MCM-6 |
(1)P 350MCM-6 |
310A, 600V |
| 552 |
(1)P 400MCM-6 |
(4)P 2-14 |
335A, 600V |
| 553 |
(1)P 400MCM-6 |
(6)P 2-14 |
335A, 600V |
| 555 |
(2)P 2/0-14 |
(6)P 4-14 |
350A, 600V |
| 559 |
(1)P 350MCM-6 |
(1)S |
350A, 600V |
| 561-CU |
(1)S |
(1)S |
230A, 600V |
| 563-CU |
(1)S |
(1)S |
230A, 600V |
| 573-CU |
(1)P 250MCM-6 |
(1)P 250MCM-6 |
255A, 600V |
| 579 |
(1)P 250MCM-6 |
(1)P 250MCM-6 |
255A, 600V |
| 587 |
(1)P 500MCM-4 |
(1)P 350MCM-6 and |
380A, 600V |
| 590 |
(1)P 2/0-14 |
(1)S |
175A, 300V |
| 953-CU |
(1)P 500MCM-4 |
(6)P 2-14 |
380A, 600V |
| 955-CU |
(2)P 2/0-14 |
(6)P 4-14 |
350A, 600V |
| 144x122-CU |
(1)S |
(2)S |
260A, 600V |
| 126 |
(1)P 350MCM-6 |
(1)P 350MCM-6 |
310A, 600V |
| 401 |
(1)P 400MCM-6 |
(6)P 2-14 |
335A, 600V |
| 551 |
(1)P 500MCM-4 |
(6)P 2-14 |
380A, 600V |
| 553-CU |
(1)S |
(1)S |
230A, 600V |
| 554 |
(1)P 350MCM-6 |
(2)P 2/0-14 |
310A, 600V |
| 557 |
(1)P 600MCM-4 |
(1)P 600MCM-4 |
420A, 600V |
| 560 |
(1)P 400MCM-6 |
(8)P 2-14 |
335A, 600V |
| 569 |
(1)P 500MCM-4 |
(2)S |
380A, 600V |
| 575 |
(1)P 500MCM-4 |
(1)S |
380A, 600V |
| 145x129 |
(2)P 350MCM-4 |
(2)P 350MCM-4 |
620A, 600V |
| 301 |
(2)P 500MCM-4 |
(2)P 500MCM-4 |
760A, 600V |
| 302 |
(2)P 500MCM-4 |
(2)P 500MCM-4 |
760A, 600V |
| 408 |
500MCM-4 |
(12)P2-14 |
760A Cu, 600V
620A A1, 600V |
| 552 |
(1)P 500MCM-4 |
(12)P 2-14 |
380A, 600V |
| 554 |
(1)P 600MCM-4 |
(1)P 600MCM-4 |
420A, 600V |
| 559 |
(2)P 500MCM-4 |
(1)S |
380A, 600V |
| 579 |
(1)P 500MCM-4 |
(6)P 2/0-14 |
380A, 600V |
| 586 |
(1)P 500MCM-6 |
(8)P 2/0-14 |
760A, 600V |
| 587 |
(1)P 500MCM-4 and |
(4)P 2/0-14 |
665A, 600V |
| 592 |
(2)P 500MCM-6 |
(12)P 4-14 |
760A, 600V |
| 594 |
(1)P 500MCM-4 |
(8)P 2-14 |
380A, 600V |
| 599 |
(2)P 500MCM-4 |
(2)S |
760A, 600V |
| 610 |
(2)P 500MCM-4 |
(1)S |
380A, 600V |
| 614 |
(1)S |
(1)S |
600A, 600V |
| ST719 |
4-8 |
4-8 |
85A, 150V |
| ST722 |
2/0-8 |
2/0-8 |
Single 115A, 300V
Dual 175A, 300V |
| 986-CU |
(2)P 500MCM-4 |
(8)P 2/0-14 |
760A, 600V |
| 992-CU |
(2)P 500MCM-4 |
(12)P 2-14 |
760A, 600V |
| 1453401 |
(6)P 500MCM-6 |
(18)P 2/0-14 |
2280A (380A per line |
| 1100 |
(1)P 6-18 |
(1)P 6-18 |
65A, 300V |
| 1100S |
(1)P 6-14 |
(1)P 6-14 |
65A, 600V |
| 1100-PS |
(1)P 6-18 |
(1)6-18 |
65A, 600V |
| 1100S-PS |
(1)P 6-18 |
(1)6-14 |
65A. 600V |
| 1103P |
(1)P 4-14 |
(1)P 4-14 |
70A, 600V |
| 1200 |
(1)P 4-18 |
(1)P 4-18 |
85A, 300V |
| 1500 |
(1)SCR 6-18 |
(1)SCR 6-18 |
75A, 600V |
| 1504116 |
(1)SCR 6-10 |
(1)SCR 6-10 |
70A, 600V |
| 1600 |
(1)SCR 6-18 |
(1)SCR 6-18 |
75A, 600V |
| 3H(or N)14 |
(1)P, SCR, TS, |
(1)P, SCR, TS, |
20A, 300V |
|
TSKK 12-18(M) |
TSKK 12-18(M) |
|
| 6H(or N)38 |
(1)P, SCR, TS, |
(1)P, SCR, TS, |
40A, 600V |
|
TSKK 10-22(M) |
TSKK 10-22(M) |
|
|
(1)P, SCR, |
(1)P, SCR, |
40A, 600V |
|
TS 8-18(M) |
TS 8-18(M) |
|
| 6G38 |
TS 8-18(M) |
TS 8-18(M) |
40A, 600V |
|
TSKK 10-22(M) |
TSKK 10-22(M) |
40A, 600V |
| 6H(or N)12 |
(1)P 4-16 |
(1)P 4-16 |
70A, 600V |
| 8500001 |
(2)P 4-14 |
(2)P 4-14 |
110A, 600V |
Legend: "(1) to (12)" Number of Terminations per Pole; "P" Pressure
Wire Connector with Set Screw; "SCR" Wire Binding Type Screw, Sems Pressure
Saddle Screw With or Without Lockwasher; "TS" Tubular Screw; "TSKK"
Tubular Screw with Pressure Pad; "SOL" Solder Terminal; "W" Wire Wrap
Terminal; "S" Stud; "T" Tapped Hole Without Screw; "QC"
Quick Connect Tab; "(M)" Multiple Combinations of Wires.
- Terminal blocks, Series 409, 2A, 300V; 410, 411, 5A, 300V; 599, 600, 609, 620, 670, 699,
700, 799, 800, 899, 912, 1590, 2590, 3590, 3690, 4590, 4690, 5590, 5690, 15A, 300V; 671,
671RZ, 701, 801, 1690, 2690, 601, 670A-RZ, 20A, 300V; 601-RZ, 20A, 600V; 602, 621RZ, 622,
672, 802, 812, 30A, 600V; 603, 803, 50A, 600V; 604, 70A, 600V; 605, 90A, 600V.
- Terminal blocks, Cat Nos EPBAD41, EPBAD44, EPBAP41, EPBAP44, EPBCD41,
EPBCD44, EPBCP41, EPBCP44, rated 195A, 600V for copper conductors, 150A,
600V for aluminum conductors.
- Terminal blocks, Cat Nos EPBAD71, EjPBAP71, EPBCD71 and EPBCP71, rated
580A, 600 for copper conductors, 460A, 600V for aluminum conductors.
- Terminal blocks, Cat Nos EPBAD74, EPBAP74, EPBCD74 and EPBCP74, rated
380A, 600V for copper conductors and 305A, 600V for alumunum conductors.
- Cat Nos 1451615 and 1453615, rated AL7CU, 600MCM to 2 AWG copper and aluminum
conductors.
Notes:
- "X"'s in the above series designations are by digits denoting the number of
poles, and suffixes may be added to denote minor variations not affecting the electrical
characteristics of the devices.
- For quick-disconnect (push-on) terminal types, electrical spacings depend upon type of
wire connector used; suitable for factory-wired connections only.
- These are Certified only for supply to manufacturers for the assembly, as components of
equipment where the suitability of the combination is determined in the end use.
- 1700 Series, for solid and/or stranded copper conductors, rated 30A and/or
75A, 600V. (See Project 1606724 for wire ranges and torque rating).
- Terminal blocks, for solid or stranded copper wire, with max electrical
ratings of catalogue numbers as follows:
|
Cat. No. |
Current |
Voltage |
Groups |
Cu Wire |
Tightening Torque |
|
0986 RZ TC |
30A |
600V |
B,C |
10-24AWG |
12 lb-in/1.36 N-m |
|
0987 RZ TC |
50A |
600V |
B,C |
8-24AWG |
12 lb-in/1.36 N-m |
Notes:
- Suffixes may be added to denote the number of poles.
- Each opening of terminal clamp for series 0986 and 0987 can accept two 12AWG
or two 14AWG or one 12AWG and one 14AWG combine, solid or stranded copper wires.
The assigned tightening torque value for this wires combination is 20 lb-in/
2.26 N-m.
- Supplied only to manufacturers, as components, for the assembly of Certified
electrical equipment, where the acceptability of suitability of the combination
is determined in the end use.
Cat No |
Current CU/AL |
Voltage |
Groups |
Wire Range AWG/
kcmil |
|
| |
|
|
|
Line |
Load |
|
FPB23570 |
175A/135A |
600V |
A,B,C |
2/0 – 14 |
(4) 4 – 14 |
|
FPB23572 |
175A/135A |
600V |
A,B,C |
2/0 – 14 |
2/0 – 14 |
|
FPB23574 |
175A/135A |
600V |
A,B,C |
2/0 – 14 |
1/4 - 20 Stud |
|
FPB23580 |
175A/135A |
600V |
A,B,C |
2/0 – 14 |
(6) 4 -14 |
|
FPB33553 |
270A/335A |
600V |
A,B,C |
400 – 6 |
(6) 2 – 14 |
|
FPB33588 |
335A/335A |
600V |
A,B,C |
600 – 2 |
(3) 1/0 – 14,
(6) 2- 14 |
|
FPB33595 |
335A/335A |
600V |
A,B,C |
600 – 2 |
(12) 4 - 14 |
|
132X122
|
200A
|
600V
|
B,C
|
¼-20
Stud
|
¼-20
Stud
|
|
132X422 |
200A
|
600V
|
B,C
|
M6
Stud
|
M6
Stud
|
|
132X474
|
175A/135A
|
600V
|
B,C
|
2/0
- 14
|
M6
Stud
|
|
132X574
|
175A/135A
|
600V
|
B,C
|
2/0
- 14
|
¼-20
Stud
|
|
132X572
|
175A/135A
|
600V
|
B,C
|
2/0
- 14
|
2/0
- 14
|
|
132X570
|
175A/135A
|
600V
|
B,C
|
2/0
- 14
|
(4)
4 - 14
|
|
132X580
|
175A/135A
|
600V
|
B,C |
2/0
- 14 |
(6)
4 - 14
|
|
132X970
|
175A
|
600V
|
B,C
|
2/0
- 14Cu
|
(4)
4 - 14Cu
|
|
132X972
|
175A
|
600V
|
B,C
|
2/0
- 14Cu
|
(1)
4 - 14Cu
|
|
EPBAD21
|
115A
|
600V
|
B,C
|
2 - 14Cu
|
2 - 14Cu
|
|
EPBAD24
|
115A
|
600V
|
B,C
|
2 - 14Cu
|
(4) 10 - 14Cu
|
Notes:
- Suffixes may be added for optional features.
- Letter "X" denoting number of poles.
- Terminal blocks with 1/4-20 or M6 stud are Certified for use only when
conductors are terminated with Certified crimped type terminals.
- Terminal Blocks are Certified for use with manufacturer assigned
tightening torque values.
- Supplied only to manufacturers, as components, for the assembly of Certified
electrical equipment, where the acceptability of suitability of the combination
is determined in the end use.
\jj